H. Sidewall SY8031
- Home
- Sentry Product: H. Sidewall SY8031
- H. Sidewall SY8031
Products Description :
Sentry Sprinklers Model SY8031 is an Automatic and or Open Standard Response, Horizontal Sidewall Sprinkler head that utilizes a frangible thermo-sensitive glass bulb to operate the sprinkler. The sprinkler is available in various finishes and temperatures. Sprinkler Model SY8031 is listed and approved for standard coverage for Light and Ordinary
hazards.
Model SY8031 is a 5.6 K-factor (80 metric) Sprinkler that is intended for use in fire sprinkler systems designed in accordance with the standard installation rules recognized by the applicable listings or approved agency. The Horizontal Sidewall Sprinkler produces a quarter-spherical water discharge pattern that is predominately directed downward and outward from the deflector.
Product Features:
Minimum Operating Pressure: 7 PSI (0.5 bar)
Maximum Working Pressure: 175 PSI (12 bar)
Factory Test: 100% @ 500 PSI (34.5 bar) Hydrostatically
Nominal K-Factor: 5.6 (80 metric)
Thread Size: 1/2” NPT
Bulb Size: 5 mm